Changes

Jump to navigation Jump to search
m
no edit summary
Line 10: Line 10:     
== Event Start: 01:42 ==
 
== Event Start: 01:42 ==
At first, we didn’t think there was a substantial issue - the power in James college was knocked out for about a second, but their UPS coped so we assumed ours would too. Some amusement was poked at YSTV for neglecting to put their web/db server on said UPS. Once we confirmed our website was inaccessible, we made our way over to investigate, but assumed v1rs0 was just rebooting.
+
At first, we didn’t think there was a substantial issue - the power in James college was knocked out for about a second, but their UPS coped so we assumed ours would too. Some amusement was poked at YSTV for neglecting to put their web/db server on said UPS. Once we confirmed our website was inaccessible, we made our way over to investigate, but assumed bits of Vanbrugh network were just rebooting.
    
We reached URY in a state of running on UPS power, so started a graceful shutdown of all servers using ACPI (i.e. the power button). We left logger2 running at this stage because of the uptime, and logger2 is a hardy-ish device that’s seen a lot anyway. Everything but that was powered down by 01:52.
 
We reached URY in a state of running on UPS power, so started a graceful shutdown of all servers using ACPI (i.e. the power button). We left logger2 running at this stage because of the uptime, and logger2 is a hardy-ish device that’s seen a lot anyway. Everything but that was powered down by 01:52.
Line 25: Line 25:     
== Problem #1: Stores Distribution Board ==
 
== Problem #1: Stores Distribution Board ==
The B16 breaker that estates told me they would upgrade to C16 last year tripped from the sudden desire of a large quantity of batteries to charge up. Turning the power back on caused a happy bright flash, some dimmed lights, then the breaker re-tripping.
+
The B16 breaker that estates told me they would upgrade to C16 last year tripped from the sudden desire of a large quantity of batteries to charge up. Turning the power back on caused the breaker to trip again.
    
Luckily, switching off the compressors and distribution amplifier for the audio path was sufficient, and the UPS then began to charge at 05:44, and enabled server power at 05:49.
 
Luckily, switching off the compressors and distribution amplifier for the audio path was sufficient, and the UPS then began to charge at 05:44, and enabled server power at 05:49.
    
== Problem #2: logger2 ==
 
== Problem #2: logger2 ==
As is traditional, logger2 decided not to play ball when we powered it up. It made strange noises and smelled a bit, so we left it off overnight. Confirmation that logger1 and uryblue were operating left us happy to power the transmitter on by 06:30. It did start up later in the day, so was probably just being fussy because it was a bit cold.
+
As is traditional, logger2 decided not to play ball when we powered it up. It made strange noises, so we left it off overnight. Confirmation that logger1 and uryblue were operating left us happy to power the transmitter on by 06:30. It did start up later in the day, so was probably just being fussy because it was a bit cold.
    
== Problem #3: IT Services Systems ==
 
== Problem #3: IT Services Systems ==

Navigation menu